$ EZ-EDS Version 3.25.1.20181218 Generated Electronic Data Sheet $ /*********************************************************/ $ /* */ $ /* EZ-EDS Version 3.3 Generated Electronic Data Sheet */ $ /* SMC EX260-SDN1 Serial Interface Unit */ $ /* */ $ /* This file was generated by SMC EX260-SDN1 designer */ $ /* (C)2009 SMC Corporation All Rights Reserved. */ $ /* */ $ /*********************************************************/ [File] DescText = "SMC EX260-SDN1 EDS File"; $ File Description Text CreateDate = 07-07-2009; $ File Creation Date CreateTime = 13:00:00; $ File Creation Time ModDate = 03-09-2019; $ Last Modification Date ModTime = 13:00:00; $ Last Modification Time Revision = 1.2; $ EDS Revision HomeURL = "http://www.smcworld.com"; $ Home URL [Device] VendCode = 7; $ Vendor Code VendName = "SMC Corp."; $ Vendor Name ProdType = 27; $ Device Type ProdTypeStr = "Pneumatic Valve(s)"; $ Device Type String ProdCode = 146; $ Product Code MajRev = 1; $ Device Major Revision MinRev = 2; $ Device Minor Revision ProdName = "EX260-SDN1"; $ Product Name Catalog = "EX260-SDN1"; $ Catalog Number Icon = "EX260-SDN1.ico"; $ Icon File Name DNetQC = 0x0001, 200; $ Quick Connect supported $ at powerup, $ 200ms power up time. [Device Classification] Class1 = DeviceNet; [IO_Info] Default = 0x0001; $ Poll Only PollInfo = 0x0001, 0, 4; $ Default Output = Output4 Input1 = 1, 0, 0x0001, "Status byte", 6, "20 04 24 69 30 03", "Diagnostic status area"; Input2 = 4, 0, 0x0001, "Status and 16pts. Input", 6, "20 04 24 6a 30 03", "Extended dummy input"; Input3 = 6, 0, 0x0001, "Status and 32pts. Input", 6, "20 04 24 6b 30 03", "Extended dummy input"; Input4 = 2, 0, 0x0001, "Status word", 6, "20 04 24 6c 30 03", "Extended diagnostics status area"; $ -- Output Connections -- Output1 = 1, 0, 0x0001, "8pts. Solenoid Output", 6, "20 04 24 22 30 03", "Output area"; Output2 = 2, 0, 0x0001, "16pts. Solenoid Output", 6, "20 04 24 23 30 03", "Output area"; Output3 = 3, 0, 0x0001, "24pts. Solenoid Output", 6, "20 04 24 24 30 03", "Output area"; Output4 = 4, 0, 0x0001, "32pts. Solenoid Output", 6, "20 04 24 25 30 03", "Output area"; [ParamClass] Object_Name = "Parameter Object"; Object_Class_Code = 0x0F; MaxInst = 4; $ Number of Parameter Descriptor = 0x0009; $ Parameter Characteristics CfgAssembly = 0; $ Not support Configuration Assembly [Params] Param1 = 0, $ Reserved, shall equal 0 6,"20 64 24 01 30 64", $ Path Size./SMC SI Obj Inst 1 Attr 64 0x003C, $ Descriptor 0xC1, $ Data Type=(BOOL) 1, $ Data Size in byte "SOLV Status", $ Parameter Name "", $ Units String "Solenoid Power Status",$ Help string 0,1,0, $ Min./ Max./ Default Value 1,1,1,0, $ Mult./ Div./ Base./ Offset scaling 0,0,0,0, $ Mult./ Div./ Base./ Offset links 0; $ Decimal places Enum1 = 0,"Solenoid Power OK", 1,"Solenoid Power ERROR"; Param2 = 0, $ Reserved, shall equal 0 6,"20 64 24 01 30 65", $ Path Size./SMC SI Obj Inst 1 Attr 65 0x003C, $ Descriptor 0xC1, $ Data Type=(BOOL) 1, $ Data Size in byte "SOLV Fuse Status", $ Parameter Name "", $ Units String "Fuse Status of Solenoid Power", $ Help string 0,1,0, $ Min./ Max./ Default Value 1,1,1,0, $ Mult./ Div./ Base./ Offset scaling 0,0,0,0, $ Mult./ Div./ Base./ Offset links 0; $ Decimal places Enum2 = 0,"Default Value", 1,"-"; Param3 = 0, $ Reserved, shall equal 0 6,"20 64 24 01 30 68", $ Path Size./SMC SI Obj Inst 1 Attr 68 0x000C, $ Descriptor 0xC1, $ Data Type=(BOOL) 1, $ Data Size in byte "Hold Clear Timeout", $ Parameter Name "", $ Units String "Setting of Hold Clear Timeout", $ Help string 0,1,0, $ Min./ Max./ Default Value 1,1,1,0, $ Mult./ Div./ Base./ Offset scaling 0,0,0,0, $ Mult./ Div./ Base./ Offset links 0; $ Decimal places Enum3 = 0,"DIP SW", 1,"EEPROM"; Param4 = 0, $ Reserved, shall equal 0 6,"20 64 24 01 30 6D", $ Path Size./SMC SI Obj Inst 1 Attr 6D 0x003C, $ Descriptor 0xC6, $ Data Type=(USINT) 1, $ Data Size in byte "EEPROM Status", $ Parameter Name "", $ Units String "EEPROM Monitor", $ Help string 0,2,0, $ Min./ Max./ Default Value 1,1,1,0, $ Mult./ Div./ Base./ Offset scaling 0,0,0,0, $ Mult./ Div./ Base./ Offset links 0; $ Decimal places Enum4 = 0,"OK", 1,"ALARM", 2,"ERROR"; [Groups] Group1 = "Diagnosis", $ Group Name 3, $ Number of Member 1,2,4; $ Param and Variant in Group Group2 = "Setting", $ Group Name 1, $ Number of Member 3; $ Param and Variant in Group [Assembly] Revision = 2; Object_Name = "Assembly Object"; Object_Class_Code = 0x04; Assem34 = "8pts. Solenoid Output", "20 04 24 22 30 03", , 0x0000, ,, 8,; Assem35 = "16pts. Solenoid Output", "20 04 24 23 30 03", , 0x0000, ,, 16,; Assem36 = "24pts. Solenoid Output", "20 04 24 24 30 03", , 0x0000, ,, 24,; Assem37 = "32pts. Solenoid Output", "20 04 24 25 30 03", 4, 0x0000, ,, 32,; Assem101 = "Fault Value", "20 04 24 65 30 03", 4, 0x0000, ,, 32,; Assem102 = "Fault Action", "20 04 24 66 30 03", 4, 0x0000, ,, 32,; Assem103 = "Idle Value", "20 04 24 67 30 03", 4, 0x0000, ,, 32,; Assem104 = "Idle Action", "20 04 24 68 30 03", 4, 0x0000, ,, 32,; Assem105 = "Diagnostic Status", "20 04 24 69 30 03", 1, 0x0000, ,, 8,; Assem106 = "Diagnostic Status and 16pts. Input", "20 04 24 6a 30 03", 4, 0x0000, ,, 32,; Assem107 = "Diagnostic Status and 32pts. Input", "20 04 24 6b 30 03", 6, 0x0000, ,, 48,; Assem108 = "Extended Diagnostic Status", "20 04 24 6c 30 03", , 0x0000, ,, 16,;